Power loss analysis on the Tantui Atas distribution network using ETAP

Authors

  • Marceau Armstrong Fillex Haurissa Politeknik Negeri Ambon
  • Farrel Aqshal Alfarizi Naca Jurusan Teknik Elektro

DOI:

https://doi.org/10.54463/je.v4i2.109

Keywords:

Distribution Network, ETAP Software, Power Loss.

Abstract

The process of distributing electricity from power plants to consumers always experiences loss of energy or power losses. Power losses are unavoidable in the distribution network system and if it exceeds the percentage it will harm the distribution network system manager in terms of power or energy distribution. There are two types of shrinkage in the electric power system, namely technical and non-technical shrinkage. Technical depreciation is depreciation that occurs as a result of impedance on generation equipment and distribution equipment in transmission and distribution so that there is lost power. This research is Survey Research, where no changes are made or there is no special treatment of the variables studied. The types of data needed to analyze this calculation are: SLD data, transformer capacity, transformer load, channel length data, conductor type and capacity. The variable used in analyzing the results of this study is the power losses in the Upper Tantui penyulang. Based on the simulation results and also the analysis of the power losses on the Upper Tantui repeater, it can be concluded that the value of power losses during WBP conditions is still in normal conditions, which is below the SPLN standard of 5%, while in the installed load conditions the value of power losses has exceeded the normal limit according to SPLN standards, which is above 5%, where in the installed load conditions the value of power losses has reached 5.48%.

Author Biographies

  • Marceau Armstrong Fillex Haurissa, Politeknik Negeri Ambon

    Jurusan Teknik Elektro

    Dosen (Gol. IVB)

  • Farrel Aqshal Alfarizi Naca, Jurusan Teknik Elektro
    Mahasiswa Teknik Elektro

References

A. Perbaikan Susut Daya Pada Jaringan Distribusi PtPln Ulp Jayapura Penyulang Bougenville, E. Margaretha Ohee Jurusan Teknik Elektro, and J. Dultudes Mangopo Jurusan Teknik Elektro, “Analysis Of Power Loss Improvements In The Distribution Network At Pt. Pln (Persero) Ulp Jayapura, Bougenville Feeder,†J. Sains dan Teknol., vol. 1, no. 2, pp. 124–135, 2022.

Y. Marniati, “Evaluasi Susut Daya Penyulang Cendana 20 kV Pada Gardu Induk Bungaran Dengan ETAP 12.6,†J. Tek. Elektro ITP, vol. 7, no. 1, pp. 79–92, 2018, doi: 10.21063/jte.2018.3133712.

Erhaneli, Z. Anthony, S. Amalia, and H. F. P. Sari, “Perbaikan Nilai Susut Teknis Jaringan Tegangan Menengah Penyulang 5 Matur PT PLN Rayon Koto Tuo,†J. Tek. Elektro Inst. Teknol. Padang, vol. 9, no. 2, pp. 67–71, 2020, [Online]. Available: https://ejournal.itp.ac.id/index.php/telektro/index

R. Rifal, S. B. Utomo, and M. Haddin, “Analisis Perhitungan Rugi-Rugi Daya pada Saluran Transmisi Tegangan Tinggi 150 kV Gardu Induk Tambak Lorok – Bawen dengan menggunakan Etap 12.6.0,†Pros. Konf. Ilm. Mhs. Unissula Klaster Eng., vol. 0, no. 0, pp. 234–243, 2020, [Online]. Available: http://lppm-unissula.com/jurnal.unissula.ac.id/index.php/kimueng/article/view/8592

J. . Stevenson, W.D and Grainger, Analysis Power System. Singapura: McGraw Hill, 1994.

P. Studi et al., “Arya Pamungkas Subuh Isnur Haryudo,†no. 5, 2006.

I. K. Winarta, E. H. Harun, and J. D. Giu, “Studi Susut Daya Jaringan Distribusi Primer Area Luwuk Melalui Simulasi Aliran Daya Menggunakan Metode Newton Raphson,†Transmisi, vol. 23, no. 4, pp. 125–133, 2021, doi: 10.14710/transmisi.23.4.125-133.

A. M. Siregar, B. Badriana, H. M. Yusdartono, and A. Hasibuan, “Perbaikan Nilai Susut Teknis Jaringan Tegangan Menengah Pada Feeder K.H. 05 (Case Study PLN ULP Kruenggukuh),†J. Energi Elektr., vol. 12, no. 1, p. 24, 2023, doi: 10.29103/jee.v12i1.11708.

Downloads

Published

2023-11-30

Issue

Section

Articles